M2000 AND C1000 SERIES CHILLER CONTROLLERS
The Chiller controllers are designed to control a variety of different chiller units and systems, and can be used for both air cooled chillers and water cooled chillers. The on-board microcontroller offers precise digital control to maximize performance. The available control sequences are fully configurable, either locally or remotely, using free software.
Specifications
- M2000 CHL AND C1000 CHL COMMON FEATURES
- Pump activity based on outside temperature or schedule (or both)
- Configurable pump exercise sequence for extended periods of inactivity
- Supply water setpoint reset based on outside temperature, return temperature or demand
- Various lead-lag sequences for the pumps and chillers
- Chiller lockout or stage down based on entering or leaving condenser water temperature limits
- Remote monitoring and configuration with FREE Prolon Focus Software
- Standalone or Networked (up to 127 nodes)
- Built-in protection sequences with configurable temperature limits and minimum delays
- M2000 CHL SPECIFIC FEATURES
- Control up to 4 chiller stages (multiple chillers or a single multi-stage chiller or combination)
- Can modulate a VFD for each pump to maintain a fixed water pressure setpoint
- Internal clock with configurable schedules and calendars
- A manual/off/auto switch for each of the eight outputs
- 5 digital outputs and 3 analog outputs equipped with resettable fuses
- Dedicated input that can deactivate the pumps upon contact closure
- C1000 CHL SPECIFIC FEATURES
- Control up to 3 chiller stages (multiple chillers or a single multistage chiller)
- 4 digital outputs and 1 analog output equipped with resettable fuses